Article 4: How to Size a PV System from an Electricity Bill
Sizing a PV System from an Electricity Bill
By- Ranveer Yadav
An
electricity bill typically reveals information about a residential or
commercial customer’s total monthly energy consumption (as we discussed in the
previous article in this series, Reading Your Electricity Bill: A
Beginner’s Guide). From this value alone, it is possible to approximate the
required size of a PV system that offsets monthly energy usage.
Take
a hypothetical monthly energy consumption of 500 kilowatt-hours, which is on
the lower end for a household in Delhi. Assuming there are 30 days in a month,
an average daily energy use value can be reached by dividing the monthly use by
30.
Daily
Energy Use=Monthly Energy Use/Days in Month=500kWh/mo30days/mo=16.7kWh/dayDaily
Energy Use
Next,
insolation values are neede1d. As mentioned in The Beginner’s Guide to
Solar Energy, insolation values are reported in kWh/m2-day. Since a
“full-sun’s” worth of incoming solar energy is approximated as 1 kW/m2,
insolation values reported in kWh/m2-day approximate the hours of
full-sun equivalent that a location receives over the course of a day.
Figure1. Visualization of how total
solar insolation received over the course of a day (left) can be represented by
number of full-sun hours (right).
For a Delhi home, the average daily
irradiance value is 5.2 kWh/m2-day. By dividing the daily energy
usage by hours a day of full sun, the power output required by the PV system is
calculated.
Power
Output=Daily Energy Use/Daily hours of full sun=16.7kWh/day5.2hours/day=3.21kWPower
Output
Figure 2. The Delhi home used for
this PV system sizing exercise.
This
would be the size of the PV system required, if our system was 100% efficient.
However, that is not the case because all PV systems have a corresponding
derating factor that takes into account the inefficiencies of the overall
system, such as soiling of the panels and imperfect electrical connections.
According
to the National Renewable Energy Laboratory’s PVWatts calculator, a typical
derate factor is 0.84. For the sake of this calculation, we assume the derate
factor be 80%, or 0.8. In order to determine the size of the PV system, divide
the required power output by the derate factor.
PV
System Size=Power Output*Derate Factor=3.21kW*0.8=4.01kWPV System Size
From
this analysis, the approximate size of a PV system required to completely
offset the average monthly energy usage of a 500 kWh/month home in Delhi would
be about 4 kW.
Comparing the
PV Size Estimation to a Simulated Result
Since
this is a rough estimate, how does it compare against an actual, comprehensive
design for a home with the same characteristics?
Using
the same conditions as above, a PV system design software found that
the required system size to be 4 kW, which is almost identical to the answer
from the estimation conducted above.
Although the answers are very close, it’s
important to note that this may not always be the case. For instance, when
there is shading on the panels, a significant reduction in power output can
occur. Although a shading term is included when calculating a derate factor, it
can fail to accurately capture the effect that shading has on a PV system’s
power output. Therefore, expect the results to be less close when modeling a
location with shading.
Comments
Post a Comment